Torque control, Related parameters – Yaskawa Matrix Converter User Manual

Page 273

Advertising
background image

6

-108

‹

Torque Control

With Flux Vector Control, the motor’s output torque can be controlled by a torque reference from an analog
input. To carry out the torque control, set d5-01 to 1 or H1-†† (Multi-function digital input) to 71 for speed
or torque control, and then turn on the contact.

„

Related Parameters

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector

d5-01

Torque Control
Selection

0: Speed control (C5-01 to C5-07)
1: Torque control
This function is only available in Flux Vector
Control method. To use the function for
switching between speed and torque control,
set to 0 and set the multi-function input to
“speed/torque control change.”

0 or 1

0

No

No

No

A

Torq Control Sel

d5-02

Torque Reference
Delay Time

Set the torque reference delay time in ms
units.
This function can be used to adjust the noise
of the torque control signal or the responsive-
ness with the host controller. When oscillation
occurs during torque control, increase the set
value.

0 to

1000

0 ms

No

No

No

A

Torq Ref Filter

d5-03

Speed Limit Selec-
tion

Set the speed limit command method for the
torque control method.
1: The analog input limit from a frequency

reference

2: Limited by d5-04 setting values.

1 or 2

1

No

No

No

A

Speed Limit Sel

d5-04

Speed Limit

Set the speed limit during torque control as a
percentage of the maximum output frequency.
This function is enabled when d5-03 is set to
2. Directions are as follows.
+: Run Command direction
-: Run Command opposite direction

-120 to

+120

0%

No

No

No

A

Speed Lmt Value

d5-05

Speed Limit Bias

Set the speed limit bias as a percentage of the
maximum output frequency.
Bias is given to the specified speed limit. It
can be used to adjust the margin for the speed
limit.

0 to 120

10%

No

No

No

A

Speed Lmt Bias

d5-06

PID Output Limit

Set the delay time from inputting the multi-
function input “speed/torque control change”
(from on to off or off to on) until the control is
actually changed, in ms units.
This function is enabled when the multi-func-
tion input “speed/torque control change” is
set. In the speed/torque control switching
timer, the analog inputs hold the values of
when the “speed/torque control change”
changes. Always be sure to allow time for this
process to finish completely.

0 to

1000

0 ms

No

No

No

A

PID Limit

H3-04

Terminal A3 Sig-
nal Level Selection

Sets the signal level of terminal A3.
0: 0 to 10 VDC
1: -10 to +10 VDC

0 or 1

0

No

A

A

A

Term A3 Signal

H3-05

Terminal A3 Func-
tion Selection

Select multi-function analog input function
for terminal A3. Refer to the next page.

0 to 1F

2

No

A

A

A

Terminal A3 Sel