Main circuit terminal functions, Main circuit configurations – Yaskawa Matrix Converter User Manual

Page 44

Advertising
background image

2

-10

‹

Main Circuit Terminal Functions

Main circuit terminal functions are summarized according to terminal symbols in Table 2.4. Wire the terminals
correctly for the desired purpose.

* 1. Connect the momentary power loss compensation unit. Do not connect power to these terminals.
* 2. Normally not used. Do not connect power to these terminals.
* 3. The MxC models CIMR-ACA4110 and 4160 do not have terminals r2, s2, t2, p1 and n1.

‹

Main Circuit Configurations

The main circuit configurations of the MxC are shown in Fig 2.7.

„

CIMR-ACA25P5 to 2045, 45P5 to 4160

* 1. Connect the momentary power loss compensation unit. Do not connect power to these terminals.
* 2. Normally not used. Do not connect power to these terminals.
* 3. The MxC models CIMR-ACA4110 and 4160 do not have terminals r2, s2, t2, p1 and n1.
Note: Control power is supplied internally from the main circuit power supply for all MxC models.

Fig 2.7 MxC Main Circuit Configurations

Table 2.4 Main Circuit Terminal Functions

(200 V class and 400 V class)

Purpose

Terminal symbols

Main circuit power input

R/L1, S/L2, T/L3

MxC output

U/T1, V/T2, W/T3

Ground

Connection to optional devices

r2

*2 *3

, s2

*2 *3

, t2

*2 *3

, p1

*1 *3

,

n1

*1 *3

t2

*

2 *3

Control
circuit

R/L1

S/L2

T/L3

U/T1

V/T2

W/T3

r2

*

2 *3

s2

*

2 *3

p1

*

1 *3

n1

*

1 *3

Input filter

Power supply