U2: fault trace – Yaskawa Matrix Converter User Manual

Page 162

Advertising
background image

5

-62

„

U2: Fault Trace

Parameter

Number

Name

Description

Output Signal

Level during Multi-

Function Analog

Output

Min.

Unit

Control

Methods

MEMO-

BUS

Register

Display

V/f

Open

Loop

Vector

Flux

Vector

U2-01

Current fault

The contents of the current fault.

No output available

-

A

A

A

80H

Current Fault

U2-02

Previous fault

The contents of the error that occurred
just prior to the current fault.

-

A

A

A

81H

Last Fault

U2-03

Reference
frequency at fault

The reference frequency when the previ-
ous fault occurred.

0.01Hz

A

A

A

82H

Frequency Ref

U2-04

Output frequency at
fault

The output frequency when the previous
fault occurred.

0.01Hz

A

A

A

83H

Output Freq

U2-05

Output current at
fault

The output current when the previous
fault occurred.

0.1 A

A

A

A

84H

Output Current

U2-06

Motor speed at fault The motor speed when the previous fault

occurred.

0.01 Hz

No

A

A

85H

Motor Speed

U2-07

Output voltage
reference at fault

The output reference voltage when the
previous fault occurred.

0.1

VAC

A

A

A

86H

Output Voltage

U2-08

Control circuit
voltage at fault

The control circuit voltage when the pre-
vious fault occurred.

1 VDC

A

A

A

87H

PS Voltage

U2-09

Output power at
fault

The output power when the previous
fault occurred.

0.1 kW

A

A

A

88H

Output kWatts

U2-10

Torque reference at
fault

The reference torque when the previous
fault occurred. The motor rated torque
corresponds to 100%.

0.1%

No

A

A

89H

Torque Reference

U2-11

Input terminal
status at fault

The input terminal status when the previ-
ous fault occurred.
The format is the same as for U1-10.

-

A

A

A

8AH

Input Term Sts

U2-12

Output terminal sta-
tus at fault

The output terminal status when the pre-
vious fault occurred. The format is the
same as for U1-11.

-

A

A

A

8BH

Output Term Sts

U2-13

Operation status at
fault

The operating status when the previous
fault occurred. The format is the same as
for U1-12.

-

A

A

A

8CH

MxC Status

U2-14

Cumulative opera-
tion time at fault

The operating time when the previous
fault occurred.

1 hr

A

A

A

8DH

Elapsed time

U2-23

*

Power voltage

Monitors the input power supply voltage
in the MxC.

10 V: 400 VAC (200 V
class)
800 VAC (400 V
class)
(0 V to 10V possible)

1VAC

A

A

A

7E8H

Power Voltage