Protective and Diagnostic Functions

7-

9

BUS

Option

Com Err

Option Communications Error
A communications error was detected
during a Run Command or while set-
ting a frequency reference from a
Communications Option Card.

-

Check the communications
devices and communications sig-
nals.

CPF00

CPF

Digital Operator Communications
Error 1
Communications with the digital oper-
ator were not established within 5 sec-
onds after the power was turned on.

The digital operator's connector isn't
connected properly.

Disconnect the digital operator
and then connect it again.

The MxC's control circuits are faulty.

Replace the MxC.

CPU External RAM Fault

-

Try turning the power supply off
and on again.

The control circuits were destroyed.

Replace the MxC.

CPF01

CPF01

Digital Operator Communications
Error 2
After communications were estab-
lished, there was a communications
error with the digital operator for more
than 2 seconds.

The digital operator isn't connected
properly.

Disconnect the digital operator
and then connect it again.

The MxC's control circuits are faulty.

Replace the MxC.

CPF03

EEPROM

Error

EEPROM Error

-

Try turning the power supply off
and on again.

The control circuit is damaged.

Replace the MxC.

CPF04
Internal

A/D Err

CPU Internal A/D Converter Error

-

Try turning the power supply off
and on again.

The control circuit is damaged.

Replace the MxC.

CPF05

External

A/D Err

CPU External A/D Converter Error

-

Try turning the power supply off
and on again.

The control circuit is damaged.

Replace the MxC.

CPF06

Option

error

Option Card Connection Error

The option card is not connected prop-
erly.

Turn off the power and insert the
card again.

The MxC or option card is faulty.

Replace the option card or the
MxC.

CPF07

RAM-Err ASIC Internal RAM Fault

-

Try turning the power supply off
and on again.

The control circuit is damaged.

Replace the MxC.

CPF08

WAT-Err

Watchdog Timer Fault

-

Try turning the power supply off
and on again.

The control circuit is damaged.

Replace the MxC.

CPF09

CPU-Err

CPU-ASIC Mutual Diagnosis Fault

-

Try turning the power supply off
and on again.

The control circuit is damaged.

Replace the MxC.

CPF10

ASIC-Err ASIC V

ersion Fault

The MxC control circuit is faulty

Replace the MxC.

Table 7.1 Fault Displays and Processing (Continued)

Display

Meaning

Probable Causes

Corrective Actions

Advertising