L3: stall prevention – Yaskawa Matrix Converter User Manual

Page 145

Advertising
background image

Parameter Tables

5-

45

„

L3: Stall Prevention

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

L3-01

*

Stall Prevention
Selection During
Accel

Selects the stall prevention method used
to prevent excessive current during accel-
eration.
0: Disabled. - Motor accelerates at

active acceleration rate. The motor
may stall if load is too heavy or accel
time is too short.

1: General Purpose - When output cur-

rent exceeds L3-02 level, acceleration
stops. Acceleration will continue
when the output current level falls
below the L3-02 level.

2: Intelligent - The active acceleration

rate is ignored. Acceleration is com-
pleted in the shortest amount of time
without exceeding the current value
set in L3-02.

0 to 2

1

No

A

A

No

48FH

4-17
6-21

StallP Accel Sel

L3-02

Stall Prevention
Level During
Acceleration

This function is enabled when L3-01 is
“1” or “2”.
MxC rated current is 100%. Decrease the
set value if stalling or excessive current
occurs with default.

0 to 200 150%

No

A

A

No

490H

4-17
6-21

StallP Accel Lvl

L3-03

Stall Prevention
Limit During
Acceleration

Sets the lower limit for stall prevention
during acceleration, as a percentage of
the rated current of the MxC, when oper-
ation is in the frequency range above E1-
06 (constant power region).

0 to 100

50%

No

A

A

No

491H

4-17
6-21

StallP CHP Lvl

L3-04

*

Stall Prevention
Selection During
Deceleration

0: Disabled. - Motor decelerates at

active deceleration rate. The motor
may stall if load is too heavy or decel
time is too short.

1: General Purpose - When output cur-

rent exceeds L3-14 level, deceleration
stops. Deceleration will continue
when the output current level falls
below the L3-14 level.

0 or 1

1

No

A

A

A

492H

6-23

StallP Decel Sel

L3-05

Stall Prevention
Selection During
Run

Selects the stall prevention method to use
to prevent MxC faults during run.
0: Disabled.- MxC runs a set frequency.

A heavy load may cause the MxC to
trip on an OC or OL fault.

1: Decel Time 1 - In order to avoid stall-

ing during heavy loading, the MxC
will decelerate at Decel time 1 (C1-
02) if the output current exceeds the
level set by L3-06. Once the current
level drops below the L3-06 level, the
MxC will accelerate back to its fre-
quency reference at the active acceler-
ation rate.

2: Decel Time 2 - Same as setting 1

except the MxC decelerates at Decel
Time 2 (C1-04).
When output frequency is 6 Hz or
less, Stall Prevention during Run is
disabled regardless of the setting in
L3-05.

0 to 2

1

No

A

No

No

493H

4-17
6-43

StallP Run Sel