Elevator and Hoist Type Applications

This section describes precautions when using the MxC for elevating machines such as elevators and
cranes.

‹

Brake On/Off Sequence

„

Brake On/Off Sequence

For the holding brake’s on/off sequence, use the following MxC output signals according to the control
method.

* 1. This example shows multi-function output terminals M1-M2 used for the holding brake on/off signal.

Do not set H2-01 to 0 (During run).

* 2. This is the standard setting range for Open Loop Vector Control. For V/f control, set to approximately the motor rated slip frequency +0.5 Hz.

If the set value is too low, the motor torque is insufficient and the load may slip when the brake is applied. Be sure to set L4-01 to a value larger than that

of E1-09 (Min. Output Frequency) and larger than that of L4-02 shown in Figure 6.82. If the set value is too large, the motor may not run smoothly

when it starts running.

* 3. The hysteresis in Frequency Detection 2 can be adjusted (from 0.1 to 0.5 Hz) by L4-02 (Speed Agree Detection Width). Change the setting to approxi-

mately 0.1 Hz if there are drops while stopping.

* 4. If using the Frequency Detection 2, set L4-01 before setting the H2-01. Otherwise, the holding brake will open when the motor stops. Also, use the Fre-

quency Detection 5 to close the holding brake when the MxC is in Baseblock.

Fig 6.82

„

Sequence Circuit Configuration

The brake on/off sequence circuit configuration is shown below.

Note: Design the sequence so that the holding brake contact is open when the sequence operation conditions are satisfied and the contact between M1 and M2

is closed (on).

Make sure that the holding brake contact is closed when the emergency stop signal or MxC fault contact output signal is on.

Fig 6.83 Brake On/Off Sequence Circuit Configuration

Control Method

Brake On/Off Signal

Brake On/Off Level Adjustment

Signal Name

Parameter

*1

Signal Name

Parameter

V/f (A1-02 = 0)

Open Loop Vector

(A1-02 = 2, default)

Frequency

Detection 2

H2-01 = 05

*4

Frequency detec-
tion level and
detection width

L4-01 = 1.0 to 3.0
Hz

*2

, L4-02 = 0.1

to 0.5 Hz

*3

Frequency

Detection 5

H2-01 = 36

*4

Flux Vector (A1-02 = 3)

During Run 2

H2-01 = 37

Zero-speed level
(off timing only)

b2-01 = 0.1 to
0.5 Hz

L4-02

L4-01

off

on

Frequency detection 2

Output frequency

Time

BR

MxC

(Forward run)

UP

DOWN

HIGH/LOW

(Reverse run)

S2

(Multi-step speed reference 2)

MA

MB

S6

Fault contacts

S1

Holding brake
auxiliary relay coil

Sequence

circuit

Energizes the brake when ON
(250 Vac 1 A or less, 30 Vdc
1 A or less)

Frequency
detection 2 or
During run

M1

M2

SC

MC