-124

Monitor Function

„

Time Chart

A time chart for the zero-servo function is given in Time Chart for Zero-Servo.

Fig 6.79 Time Chart for Zero-Servo

„

Application Precautions

Be sure to leave the Run Command input on. If the Run Command is turned off, the output will be inter-
rupted and the zero-servo function will be disabled.

The holding force of the zero-servo is adjusted in b9-01. The holding force will increase if the value of the
setting is increased, but oscillation and hunting will occur if the setting is too large. Adjust b9-01 after
adjusting the speed control gain.

The zero-servo detection width is set as the allowable position offset from the zero-servo start position. Set
4 times the number of pulses from the PG.

The Zero-servo End signal will go off when the Zero-Servo Command is turned off.

Parameter

Number

Name

Description

Output Signal Level

During Multi-Function

Analog Output

Min.

Unit

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector

U1-35

Zero-Servo move-
ment pulses

Shows the number of PG pulses times
4 for the movement range when
stopped at zero.

No output available

1

No

No

A

Zero Servo Pulse

IMPORTANT

Do not lock the servo for extended periods of time at 100% when using the zero-servo function. MxC errors
may result. Extended periods of servo lock can be achieved by ensuring that the current during the servolock
is 70% or less or by increasing the MxC output capacity.

Run Command

on

off

Zero servo command

Frequency (speed) reference

Excitation level

b2-01

Motor speed

Zero Servo End signal

Zero-servo status