Related parameters „ setting precautions, Setting the droop control gain – Yaskawa Matrix Converter User Manual

Page 287

Advertising
background image

6

-122

„

Related Parameters

„

Setting Precautions

Droop Control is disabled if b7-01 is set to 0.0.

Set b7-01 to the amount of slip as the percentage of slip when the maximum output frequency is input and
the rated torque is generated.

Parameter b7-02 is used to adjust the responsiveness of Droop Control. Increase this setting if oscillation
or hunting occur.

Disable the feed forward control (n5-01 = 0) when using the droop control function.

„

Setting the Droop Control Gain

Set the droop control gain as the speed reduction at a 100% motor torque, as a percentage of the maximum
output frequency.

Fig 6.78 Droop Control Gain

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector

b7-01

Droop Control
Level

Sets the speed decrease as a percentage of
motor base speed (E1-06) when the motor is
at 100% load torque. Setting of 0.0 disables
droop control.

0.0 to
100.0

0.0

Yes

No

No

A

Droop Quantity

b7-02

Droop Control
Delay Time

Determines the droop control delay time in
response to a load change.

0.03 to

2.00

0.05 s

Yes

No

No

A

Droop Delay Time

Torque

Speed

Speed reference

0

100%

b7-01

Advertising