Yaskawa Matrix Converter User Manual

Page 159

Advertising
background image

Parameter Tables

5-

59

U1-13

Cumulative opera-
tion time

Monitors the total operating time
of the MxC.
The initial value and the operating
time/power on time selection can
be set in o2-07 and o2-08.

No output available

1

hr

A

A

A

4CH

Elapsed Time

U1-14

Software No.
(flash memory)

(Manufacturer’s ID number)

No output available

-

A

A

A

4DH

FLASH ID

U1-15

Terminal A1 input
voltage

Monitors the input voltage of the
voltage frequency reference. An
input of 10 V corresponds to
100%.

10 V: 100% (10 V)
(

−10 V to + 10 V possible)

0.1%

A

A

A

4EH

Term A1 Level

U1-16

Terminal A2 input
voltage

Monitors the input voltage of the
multi-function analog input.
An input of 10 V corresponds to
100%.

10 V: 100% (10 V)
(

−10 V to + 10 V possible)

0.1%

A

A

A

4FH

Term A2 Level

U1-17

Terminal A3 input
voltage

Monitors the input voltage of the
multi-function analog input.
An input of 10 V corresponds to
100%.

10 V: 100% (10 V)
(

−10 V to + 10 V possible)

0.1%

A

A

A

50H

Term A3 Level

U1-18

Motor secondary
current (Iq)

Monitors the calculated value of
the motor secondary current.
The motor rated secondary cur-
rent corresponds to 100%.

10 V: Motor rated secondary
current)
(

−10 V to + 10 V possible)

0.1%

A

A

A

51H

Mot SEC Current

U1-19

Motor exciting
current (Id)

Monitors the calculated value of
the motor excitation current.
The motor rated secondary cur-
rent corresponds to 100%.

10 V: Motor rated secondary
current)
(

−10 V to + 10 V possible)

0.1%

No

A

A

52H

Mot EXC Current

U1-20

Output frequency
after soft-start

Monitors the output frequency
after a soft start.
The frequency given does not
include compensations, such as
slip compensation.
The unit is set in o1-03.

10 V: Max frequency
(

−10 V to + 10 V possible)

0.01

Hz

A

A

A

53H

SFS Output

U1-21

ASR input

Monitors the input to the speed
control loop.
The maximum frequency corre-
sponds to 100%.

10 V: Max frequency
(

−10 V to + 10 V possible)

0.01

%

No

No

A

54H

ASR Input

U1-22

ASR output

Monitors the output from the
speed control loop.
The motor rated secondary cur-
rent corresponds to 100%.

10 V: Motor rated secondary
current)
(

−10 V to + 10 V possible)

0.01

%

No

No

A

55H

ASR Output

U1-24

PID feedback
value

Monitors the feedback value
when PID control is used.
The input for the max frequency
corresponds to 100%.

10 V: Max frequency
(

−10 V to + 10 V possible)

0.01

%

A

A

A

57H

PID Feedback

U1-25

DI-16H2 input sta-
tus

Monitors the reference value from
a DI-16H2 digital reference card.
The value will be displayed in
binary or BCD depending on
parameter F3-01.

No output available

-

A

A

A

58H

DI-16 Reference

U1-26

Output voltage ref-
erence (Vq)

Monitors the MxC internal volt-
age reference for motor secondary
current control.

10 V: 200 VAC (400 VAC)
(

−10 V to + 10 V possible)

0.1

VAC

No

A

A

59H

Voltage Ref (Vq)

Parameter

Number

Name

Description

Output Signal Level

during Multi-Function

Analog Output

Min.

Unit

Control

Methods

MEMO-

BUS

Register

Display

V/f

Open

Loop

Vector

Flux

Vector

Advertising