Changing frequency reference and display units – Yaskawa Matrix Converter User Manual

Page 291

Advertising
background image

6

-126

„

Changing Frequency Reference and Display Units

Set the digital operator frequency reference and display units using parameter o1-03. You can change the units
for the following parameters using o1-03.

U1-01 (shows the frequency reference)

U1-02 (shows the output frequency)

U1-05 (shows the motor speed)

U1-20 (shows the output frequency after Soft Start)

d1-01 to d1-17 (frequency reference parameters)

„

Switching between Monitors when the Power Supply is On

Using parameter o1-02, select the monitor item (U1-†† [status monitor]) to be displayed on the digital oper-
ator when the power supply is turned on. For information on monitors that may be displayed, refer to U1-††
in Chapter 5 Parameters and Settings.

Setting Precautions

If selecting monitor parameters other than U1-01 (shows the frequency reference), U1-02 (shows the output
frequency), and U1-03 (shows the output current), first select the monitor items to be displayed in o1-01, and
then set o1-02 to 4.

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector

o2-03

User Parameter
Default Value

Allows storing of parameter settings as a User
Initialization Selection.
0: No Change
1: Set Defaults - Saves current parameter set-

tings as user initialization. A1-03 now
allows selecting <1110> for user initial-
ization and returns o2-03 to zero.

2: Clear All - Clears the currently saved user

initialization. A1-03 no longer allows
selecting <1110> and returns o2-03 to
zero.

0 to 2

0

No

A

A

A

User Defaults

o2-05

Frequency Refer-
ence Setting
Method Selection

Determines if the DATA/ENTER key must be
used to input a frequency reference from the
digital operator.
0: Disabled. - DATA/ENTER key must be

pressed to enter a frequency reference.

1: Enabled. - DATA/ENTER key is not

required. The frequency reference is
adjusted by the up and down arrow keys
on the digital operator without having to
press the DATA/ENTER key.

0 or 1

0

No

A

A

A

Operator M.O.P.

o2-07

Cumulative Opera-
tion Time Setting

Sets the initial value of the elapsed operation
timer U1-13.

0 to

65535

0 hr

No

A

A

A

Elapsed Time Set

o2-10

Cumulative Cool-
ing Fan Operation
Time Setting

Set the initial value of the fan operation time
using time units.
The operation time accumulates from the set
value.

0 to

65535

0 hr

No

A

A

A

Fan ON Time Set