L8: hardware protection – Yaskawa Matrix Converter User Manual

Page 149

Advertising
background image

Parameter Tables

5-

49

„

L8: Hardware Protection

* The default depends upon the MxC capacity. The value for a 200 V class MxC of 5.5 kW is given.

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

L8-02

Overheat Alarm
Level

When the cooling fin temperature
exceeds the value set in this parameter, an
Overheat Alarm (OH) will occur.

50 to

130

90

°C

*

No

A

A

A

4AEH

6-66

OH Pre-Alarm
Lvl

L8-03

Overheat Pre-
Alarm Operation
Selection

Selects the MxC operation upon an OH
pre-alarm detection.
0: Decelerate to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

3

No

A

A

A

4AFH

6-66

OH Pre-Alarm
Sel

L8-07

Output Phase
Loss Protection

Selects the detection method for output
phase loss.
When applied motor capacity is too small
for MxC capacity, output phase loss may
be detected inadvertently. In this case, set
to 0.
0: Disabled.
1: Single Phase Loss Detection
2: 2/3-phase Loss Detection

0 to 2

0

No

A

A

A

4B3H

-

Ph Loss Out Sel

L8-09

Output Ground
Fault Detection
Selection

Enables and disables the MxC's output
ground fault detection.
0: Disabled.
1: Enabled.

0 or 1

1

No

A

A

A

4B5H

-

Ground Fault Sel

L8-10

Heatsink Cooling
Fan Operation
Selection

Controls the heatsink cooling fan opera-
tion.
0: Fan On-Run Mode - Fan will operate

only when the MxC is running and for
L8-11 seconds after RUN is removed.

1: Fan always on - Cooling fan operates

whenever the MxC is powered up.

0 or 1

0

No

A

A

A

4B6H

-

Fan On/Off Sel

L8-11

Heatsink Cooling
Fan Operation
Delay Time

This parameter sets the delay time for the
cooling fan turn off after the Run Com-
mand is removed when L8-10 = 0.

0 to 300

60 s

No

A

A

A

4B7H

-

Fan Delay Time

L8-12

Ambient Temper-
ature Setting

When the MxC is installed in an ambient
temperature exceeding its rating, the
MxC overload (OL2) protection level is
adjusted.

45 to 60 45

°C

No

A

A

A

4B8H

-

Ambient Temp

L8-15

OL2 Characteris-
tic Selection at
Low Speeds

This parameter assists in protecting the
output transistors from overheating when
output current is high and output fre-
quency is low (6 Hz and less).
0: Disabled. - L8-16 and L8-17 are dis-

abled.

1: Enabled. - L8-16 and L8-17 are

active.

0 or 1

1

No

A

A

A

4BBH

-

OL2 Sel @ L-Spd

L8-42

Factory adjust-
ment 1

For factory adjustment
Do not change the setting.
0: Not adjusted
1: Being adjusted
2: Adjusted

0 to 2

2

No

A

A

A

4F3H

8-3