Fault (ON: Digital operator communications error or fault other than CPF00 and
CPF01 has occurred).

Yes

Yes

Yes

-

F

Not used (Set when the terminals are not used).

-

-

-

-

10

Minor fault (ON: Alarm displayed)

Yes

Yes

Yes

-

11

Fault Reset Command active

Yes

Yes

Yes

-

12

Timer function output

Yes

Yes

Yes

6-93

13

Frequency agree 2 (L4-04 used)

Yes

Yes

Yes

6-45

14

Desired frequency agree 2 (ON: Output frequency = L4-03, L4-04 used, and during
frequency agree)

Yes

Yes

Yes

6-45

15

Frequency detection 3 (ON: Output frequency

≤ -L4-03, L4-04 used)

Yes

Yes

Yes

6-45

16

Frequency detection 4 (ON: Output frequency

≥ -L4-03, L4-04 used)

Yes

Yes

Yes

6-45

17

Overtorque/undertorque detection 1 NC (NC Contact: Torque detection at off)

Yes

Yes

Yes

6-49

18

Overtorque/undertorque detection 2 NO (NO Contact: Torque detection at on)

Yes

Yes

Yes

6-49

19

Overtorque/undertorque detection 2 NC (NC Contact: Torque detection at off)

Yes

Yes

Yes

6-49

1A

During reverse run (ON: During reverse run)

Yes

Yes

Yes

-

1B

During baseblock 2 (OFF: During baseblock)

Yes

Yes

Yes

-

1C

Motor selection (Motor 2 selected)

Yes

Yes

Yes

-

1D

During regeneration (ON: During regeneration)

No

No

Yes

-

1E

Restart enabled (ON: Restart enabled.)

Yes

Yes

Yes

6-65

1F

Motor overload (OL1, including OH3) pre-alarm (ON: 90% or more of the detection
level)

Yes

Yes

Yes

6-51
6-78

20

MxC overheat (OH) pre-alarm (ON: Temperature exceeds L8-02 setting)

Yes

Yes

Yes

6-78

2F

*

Maintenance Time
ON: The operation time of either the capacitors on the PCB board or the cooling fan
have reached the specified maintenance time.

Yes

Yes

Yes

6-155

30

During torque limit (current limit) (ON: During torque limit)

No

Yes

Yes

-

31

During speed limit (ON: During speed limit)

No

No

Yes

6-78

32

Speed control circuit operating for torque control (except when stopped).
The external torque reference will be limited if torque control is selected (internal
torque reference < external torque reference).
Output when the motor is rotating at the speed limit.

No

No

Yes

6-109

33

Zero-Servo Complete (ON: Zero-servo function completed)

No

No

Yes

6-78

6-123

36

Frequency (FOUT) detection 5 (ON: Output frequency is equal to or greater than the
set value of +L4-01 or equal to or less than the set value of

−L4-01 and L4-02 is used,

off during base blocked)

Yes

Yes

Yes

6-44

37

During Run 2 (ON: Frequency output, off: Baseblock, DC Injection Braking, initial
excitation, operation stop)

Yes

Yes

Yes

6-77

Set

Value

Function

Control

Methods

Page

V/f

Open

Loop

Vector

Flux

Vector