Hold analog frequency using user-set timing – Yaskawa Matrix Converter User Manual

Page 239

Advertising
background image

6

-74

‹

Hold Analog Frequency Using User-set Timing

When one of H1-01 to H1-10 (Terminal S3 to S12 Function Selection) is set to 1E (Sample/Hold Analog Fre-
quency Command), the analog frequency reference will be held from 100 ms after the terminal is turned on,
and operation will continue thereafter at that frequency.

Fig 6.53 Sample/Hold Analog Frequency

„

Precautions

When setting and executing sample and hold for analog frequency references, observe the following precau-
tions.

Setting Precautions

When using sample/hold of analog frequency reference, the following commands cannot be used at the same
time. If these commands are used at the same time, operation error OPE03 (invalid multi-function input selec-
tion) will occur.

Accel/Decel Ramp Hold Command

UP/DOWN Command

Trim Control Increase/Decrease Command

Application Precautions

When performing sample/hold of analog frequency references, be sure to store references of 100 ms mini-
mum. If the reference time is less than 100 ms, the frequency reference will not be held.

The analog frequency reference that is held will be deleted when the power supply is turned off.

‹

Switching Operations between a Communications Option Card and Con-
trol Circuit Terminals

Switch reference input between the Communications Option Card and the control circuit terminals. Set one of
the parameters H1-01 to H1-10 (Terminal S3 to S12 Function Selection) to 2 (Option/MxC selection) to
enable switching reference input using the terminal on/off status when the MxC is stopped.

Sample/Hold

Command

Analog input

Frequency reference

The analog value 100 ms after the command is turned on is used as the frequency reference.

on

on

on

100

ms

100

ms

100

ms

Advertising