Acceleration and Deceleration Characteristics

6-

17

Acceleration and Deceleration Characteristics

This section explains the acceleration and deceleration characteristics of the MxC.

‹

Setting Acceleration and Deceleration Times

The “acceleration time” refers to the time it takes for the output frequency to climb from 0% to 100%, while
“deceleration time” refers the time taken for the output frequency drop down to 0%. The default acceleration
time is C1-01, and the default of the deceleration time is C1-02.

„

Related Parameters

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector

C1-01

Acceleration Time
1

Sets the time to accelerate from zero to maxi-
mum frequency.

0.0 to

6000.0

*

10.0 s

Yes

Q

Q

Q

Accel Time 1

C1-02

Deceleration Time
1

Sets the time to decelerate from maximum
frequency to zero.

Yes

Q

Q

Q

Decel Time 1

C1-03

Acceleration Time
2

Sets the time to accelerate from zero to maxi-
mum frequency when selected via a multi-
function input.

Yes

A

A

A

Accel Time 2

C1-04

Deceleration Time
2

Sets the time to decelerate from maximum
frequency to zero when selected via a multi-
function input.

Yes

A

A

A

Decel Time 2

C1-05

Acceleration Time
3

Sets the time to accelerate from zero to maxi-
mum frequency when selected via a multi-
function input.

No

A

A

A

Accel Time 3

C1-06

Deceleration Time
3

Sets the time to decelerate from maximum
frequency to zero when selected via a multi-
function input.

No

A

A

A

Decel Time 3

C1-07

Acceleration Time
4

Sets the time to accelerate from zero to maxi-
mum frequency when selected via a multi-
function input.

No

A

A

A

Accel Time 4

C1-08

Deceleration Time
4

Sets the time to decelerate from maximum
frequency to zero when selected via a multi-
function input.

No

A

A

A

Decel Time 4

C1-10

Accel/Decel Time
Setting Units

Sets the setting resolution of C1-01 to C1-09.
0: 0.01 s (0.00 to 600.00 s)
1: 0.1 s (0.0 to 6000.0 s)

0 or 1

1

No

A

A

A

Acc/Dec Units

C1-11

Accel/Decel
Switch Frequency

Sets the frequency for automatic switching of
accel/decel times.
Fout < C1-11: Accel/Decel Time 4
Fout

≥C1-11: Accel/Decel Time 1

Multi-function inputs “Multi-Acc/Dec 1” and
“Multi-Acc/Dec 2” have priority over C1-11.
Note: With Multi-Function Input, Accel/

Decel Time 1 and 2 will take prece-

dence.

0.0 to
120.0

0.0 Hz

No

A

A

A

Acc/Dec SW Freq