Wiring control circuit terminals, Wire gauges and closed-loop connectors – Yaskawa Matrix Converter User Manual

Page 51

Advertising
background image

Wiring Control Circuit Terminals

2-

17

Wiring Control Circuit Terminals

‹

Wire Gauges and Closed-Loop Connectors

For remote operation using an analog signal, keep the control line length between the digital operator or oper-
ation signals and the MxC to 50 m or less, and separate the lines from high-power lines (main circuits or relay
sequence circuits) to reduce induction from peripheral devices.

When setting frequencies from an external device (i.e., not from the digital operator), use shielded twisted-pair
wires and ground the shield to terminal E (G), as shown in the following diagram.

Fig 2.17

Terminal numbers and wire gauges are shown in Table 2.6.

* 1. Use shielded twisted-pair cables to input an external frequency reference.
* 2. Refer to Table 2.3 Closed-Loop Connector Sizes (JIS C2805) (200 V class and 400 V class) for suitable closed-loop crimp terminal sizes for the wires.
* 3. Yaskawa recommends using a straight solderless terminal on signal lines to simplify wiring and improve reliability.

Table 2.6 Terminal Numbers and Wire Gauges (Same for all Models)

Terminals

Terminal

Screws

Tightening

Torque

(N•m)

Possible Wire

Gauges

mm

2

(AWG)

Recom-

mended

Wire Gauge

mm

2

(AWG)

Wire Type

FM, AC, AM, P1, P2,

PC, SC, A1, A2, A3, +V,

-V, S1, S2, S3, S4, S5, S6,

S7, S8, MA, MB, MC,

M1, M2

M3.5

0.8 to 1.0

0.5 to 2

*2

(20 to 14)

0.75
(18)

• Shielded, twisted-pair wire

*1

• Shielded, polyethylene-cov-

ered, vinyl sheath cable
(KPEV-S by Hitachi Electri-
cal Wire or equivalent)

P3, C3, P4, C4, R+, R-,

S9, S10, S11, S12, S+, S-,

IG

Phoenix

type

0.22 to 0.25

Single wire

*3

:

0.25 to 1.5
(24 to 16)
Stranded wire:
0.25 to 1.0
(24 to 17)

0.75
(18)

E (G)

M3.5

0.8 to 1.0

0.5 to 2

*2

(20 to 14)

1.25
(12)

E(G)

+V

A1

A2

A3

AC

Shield terminal

Speed setting power supply, +15 V 20 mA

Master speed reference, -10 to 10 V

Master speed reference, 4 to 20 mA

Auxiliary reference -10 to 10 V

Analog common

2 k

Ω

2 k

Ω

2 k

Ω

2 k

Ω

Advertising