Estimated Speed Search

The time chart for estimated speed searches is shown below.

Search at Startup

The time chart for when speed search at startup and speed search to multi-function input terminals is shown
below.

Fig 6.43 Speed Search at Startup (Estimated Speed)

Speed Search after Short Baseblock (during Power Loss Recovery, etc.)

Loss Time Shorter Than the Momentary Power Loss Minimum Baseblock Time (L2-03)

Fig 6.44 Speed Search after Baseblock (When Estimated Speed: Loss Time Is Set in L2-03)

off

on

b3-02

1.0 s

Run Command

Output frequency

Output current

Start using
speed detected

Set frequency
reference

* Lower limit set using Speed Search Delay Time (b3-05).

Minimum Baseblock Time (L2-03)

Note: If the stopping method is set to coast to stop, and the Run Command turns on in a short time,
the operation may be the same as the search in External Speed Search Command 2.

AC power supply

Output frequency

Output current

off

on

Start using
speed detected

Set frequency
reference

Minimum Baseblock Time (L2-03)

10 ms

* After AC power supply recovery, motor waits for the
minimum Speed Search Delay Time (b3-05).

*