Coast to stop – Yaskawa Matrix Converter User Manual

Page 178

Advertising
background image

Stopping Methods

6-

13

The operation after the MxC has brought the motor to stop depends on the setting of b1-05 when using Flux
Vector Control (A1-02 = 3).

Fig 6.13 Decelerate to Stop (for Flux Vector Control)

Setting Precautions

When using Flux Vector Control, the zero-speed control starts when motor speed drops to b2-01 during
deceleration. Also, the setting b2-01

< E1-09 is possible.

The current level during injection brake time at start is the value of E2-03 (Motor No-Load Current).
Accordingly, b2-02 is invalid in Flux Vector Control.

„

Coast to Stop

If the Stop Command is input (i.e., the Run Command is turned off) when b1-03 is set to 1, the MxC output
voltage will be interrupted. The motor coasts to a stop at the deceleration rate that counterbalances load inertia
and prevents damage to the application.

Fig 6.14 Coast to Stop

Injection brake
time at start

b2-03

Zero speed
control

b2-04

Baseblock

b2-03

b2-04

b2-03

b2-04

b2-03

b2-04

Run Command off

on

off

Frequency reference
via analog input

0

E1-09

b1-05=0

(frequency reference)

Run Command turns off
and zero-speed control start
when motor speed drops to b2-01.

b1-05=1

(Coast)

b1-05=2

(Run on E1-09)

b1-05=3

(Zero-speed)

Injection brake
time at start

Injection brake
time at start

Injection brake
time at start

Baseblock

Baseblock

Baseblock

Baseblock

Baseblock

Baseblock

Baseblock

Zero speed
control

Zero speed control

Zero speed control

Frequency reference drops to less
than E1-09 and zero-speed control
starts when motor speed drops to
b2-01.

Run Command turns off
and zero-speed control start
when motor speed drops to b2-01.

Run Command turns off
and zero-speed control start
when motor speed drops to b2-01.

Output frequency

Run Command

on

off

MxC output frequency interrupted

Advertising