Individual Functions

6-

91

Note: Communications error details are stored until an fault reset is input (you can also reset while the Unit is operating).

Broadcast Data

The following table shows the broadcast data. You can also write this data.

Note: Bit signals not defined in the broadcast operation signals use local node data signals continuously.

„

ENTER Command

When writing parameters to the MxC from the PLC using MEMOBUS communications, the parameters are
temporarily stored in the parameter data area in the MxC. To enable these parameters in the parameter data
area, use the ENTER Command.

There are two types of ENTER Commands: ENTER Commands that enable parameter data in RAM, and
ENTER Commands that write data to EEPROM (non-volatile memory) in the MxC at the same time as
enabling data in RAM.

The following table shows the ENTER Command data. ENTER Command data can only be written.

The ENTER Command is enabled by writing 0 to register number 0900H or 0901H.

003DH

Communications error details

Bit 0

CRC error

Bit 1

Invalid data length

Bit 2

Not used

Bit 3

Parity error

Bit 4

Overrun error

Bit 5

Framing error

Bit 6

Time-out

Bits 7 to F

Not used

003EH

kVA setting

003FH

Control method

Register
Address

Contents

0001H

Operation signal

Bit 0

Run Command 1: Operating 0: Stopped

Bit 1

Reverse Operation Command 1: Reverse 0: Forward

Bits 2 and 3

Not used

Bit 4

External fault 1: Error (set using H1-01)

Bit 5

Fault reset 1: Reset Command (set using H1-02)

Bits 6 to B

Not used

Bit C

Multi-function digital input terminal S5 input

Bit D

Multi-function digital input terminal S6 input

Bit E

Multi-function digital input terminal S7 input

Bit F

Multi-function digital input terminal S8 input

0002H

Frequency ref-
erence

30000/100%

Register No.

Contents

0900H

Write parameter data to EEPROM

0910H

Parameter data is not written to EEPROM, but refreshed in RAM only.

INFO

EEPROM can be written to from MxC a maximum of 100,000 times. Refrain from writing excessively to the
EEPROM using the Enter Commands (0900H).
The ENTER Command registers are write-only. Consequently, if reading these registers, the register address
will become invalid (Error code: 02H).