Yaskawa Matrix Converter User Manual

Page 253

Advertising
background image

6

-88

„

Data Tables

The data tables are shown below. The types of data are as follows: Reference data, monitor data, and broadcast
data.

Reference Data

The reference data table is shown below. You can both read and write reference data.

Note: Write 0 to all unused bits. Also, do not write data to reserved registers.

Register No.

Contents

0000H

Not used

0001H

Frequency reference

Bit 0

Forward Run/Stop Command 1: Forward run 0: Stop

Bit 1

Reverse Run/Stop Command 1: Reverse run 0: Stop

Bit 2

External fault

1: Error (EFO)

Bit 3

Fault reset

1: Reset Command

Bit 4

ComNet

Bit 5

ComCtrl

Bit 6

Multi-Function Input Command 3

Bit 7

Multi-Function Input Command 4

Bit 8

Multi-Function Input Command 5

Bit 9

Multi-Function Input Command 6

Bit A

Multi-Function Input Command 7

Bit B

Multi-Function Input Command 8

Bit C

Multi-Function Input Command 9

Bit D

Multi-Function Input Command 10

Bit E

Multi-Function Input Command 11

Bit F

Multi-Function Input Command 12

0002H

Frequency reference (Set units using parameter o1-03)

0003H

Not used

0004H

Not used

0005H

Not used

0006H

PID target value

0007H

Analog output 1 setting (-11 V/-1540 to 10 V/1540)

0008H

Analog output 2 setting (-11 V/-1540 to 11 V/1540)

0009H

Multi-function digital output setting

Bit 0

Contact output (Terminal M1-M2)

1: on

0: off

Bit 1

PHC1 (Contact P1-PC)

1: on

0: off

Bit 2

PHC2 (Contact P2-PC)

1: on

0: off

Bit 3

PHC3 (Contact P3-C3)

1: on

0: off

Bit 4

PHC4 (Contact P4-C4)

1: on

0: off

Bit 5

Not used

Bit 6

Set error contact (terminal MA-MC) output using bit 7. 1: on 0: off

Bit 7

Error contact (terminal MA-MC)

1: on 0: off

Bits 8 to F

Not used

000AH to 000EH Not used

000FH

Reference selection settings

Bit 0

Not used

Bit 1

Use MEMOBUS 0006H PID target value

Bits 2 to B

Not used

C

Broadcast data terminal S5 input 1: Enabled. 0: Disabled.

D

Broadcast data terminal S6 input 1: Enabled. 0: Disabled.

E

Broadcast data terminal S7 input 1: Enabled. 0: Disabled.

F

Broadcast data terminal S8 input 1: Enabled. 0: Disabled.

Advertising