E2: motor setup – Yaskawa Matrix Converter User Manual

Page 126

Advertising
background image

5

-26

„

E2: Motor Setup

* 1. The default depends on the MxC capacity. The value for a 200 V class MxC of 5.5 kW is given.
* 2. The setting range is from 10% to 200% of the MxC rated output current. The value for a 200 V class MxC for 5.5 kW is given. The upper limit of the Motor No-

Load Current (E2-03) must be less than the Motor Rated Current (E2-01).

* 3. The setting range depends on the MxC capacity. The value for a 200 V class MxC of 5.5 kW is given.

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

E2-01

Motor Rated
Current

Sets the motor nameplate full load current
in amperes (A). This value is automati-
cally set during Auto-Tuning.

2.70 to

54.00

*2

19.60

A

*1

No

Q

Q

Q

30EH

4-5

6-51

6-102

Motor Rated FLA

E2-02

Motor Rated Slip

Sets the motor rated slip in hertz (Hz).
This value is automatically set during
Rotational Auto-Tuning.

0.00 to

20.00

1.50

Hz

*1

No

A

A

A

30FH

6-100
6-102

Motor Rated Slip

E2-03

Motor No-Load
Current

Sets the magnetizing current of the motor
as a percentage of full load amps (E2-01).
This value is automatically set during
Rotational Auto-Tuning.

0.00 to

19.59

*3

5.10 A

*1

No

A

A

A

310H

6-102

No-Load Current

E2-04

Number of Motor
Poles

Sets the number of motor poles. This
value is automatically set during Auto-
Tuning.

2 to 48 4 poles

No

No

No

Q

311H

6-102

Number of Poles

E2-05

Motor Line-to-
Line Resistance

Sets the phase-to-phase motor resistance
in ohms. This value is automatically set
by Auto-Tuning.

0.000

to

65.000

0.399

Ω

*1

No

A

A

A

312H

6-102

Term Resistance

E2-06

Motor Leakage
Inductance

Sets the voltage drop due to motor leak-
age inductance as a percentage of motor
rated voltage. This value is automatically
set during Auto-Tuning.

0.0 to

40.0

18.2%

*1

No

No

A

A

313H

6-102

Leak Inductance

E2-07

Motor Iron-core
Saturation Coeffi-
cient 1

Sets the motor iron saturation coefficient
at 50% of magnetic flux. This value is
automatically set during Rotational Auto-
Tuning.

0.00 to

0.50

0.50

No

No

A

A

314H

6-102

Saturation Comp1

E2-08

Motor Iron-core
Saturation Coeffi-
cient 2

Sets the motor iron saturation coefficient
at 75% of magnetic flux. This value is
automatically set during Rotational Auto-
Tuning.

0.50 to

0.75

0.75

No

No

A

A

315H

6-102

Saturation Comp2

E2-09

Motor Mechani-
cal Loss

Sets the motor mechanical loss as a per-
centage of motor rated power (kW)
capacity.
Adjust in the following circumstances:
• When torque loss is large due to motor

bearing friction.

• When the torque loss in the load is

large.

0.0 to

10.0

0.0%

No

No

A

A

316H

-

Mechanical Loss

E2-10

Motor Iron Loss
for Torque Com-
pensation

Sets the motor iron loss in watts (W).

0 to

65535

172 W

*1

No

A

No

No

317H

6-102

Tcomp Iron Loss

E2-11

Motor Rated
Output

Sets the motor rated power in kilowatts
(kW). This value is automatically set dur-
ing Auto-Tuning.

5.50 to
650.00

5.50

kW

*1

No

Q

Q

Q

318H

-

Mtr Rated Power

E2-12

Motor Iron-Core
Saturation Coeffi-
cient 3

Set to the motor iron saturation coeffi-
cient at 130% of magnetic flux.

1.30 to

1.60

1.30

No

No

A

A

328H

6-102

Saturation Comp3