D6: field weakening – Yaskawa Matrix Converter User Manual

Page 124

Advertising
background image

5

-24

„

d6: Field Weakening

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

d6-01

Magnetic Field
Weakening Level

Set the MxC output voltage when the
field weakening command is input.
It is enabled when the field weakening
command is set for a multi-function
input.
Set the level as a percentage taking the
voltage set in the V/f pattern as 100%.

0 to 100

80%

No

A

No

No

2A0H

-

Field-Weak Lvl

d6-02

Magnetic Field
Frequency

Set the lower limit in hertz of the fre-
quency range where field control is valid.
The field weakening command is valid
only at frequencies above this setting and
only when the speed is in agreement with
the current speed reference.

0.0 to
120.0

0.0 Hz

No

A

No

No

2A1H

-

Field-Weak Freq

d6-03

Magnetic Field
Forcing Function
Selection

Set the field forcing function.
0: Disabled
1: Enabled

0 or 1

0

No

No

A

A

2A2H

-

Field Force Sel

d6-06

Magnetic Field
Forcing Limit

Set the excitation current reference’s
upper limit for field forcing. Set the limit
as a percentage, taking the motor’s no-
load current as 100%. Enabled for opera-
tion other than DC excitation.
Usually, there is no need to change this
setting.

100 to

400

400%

No

No

No

A

2A5H

-

FieldForce Limit