Setting precautions – Yaskawa Matrix Converter User Manual

Page 222

Advertising
background image

Continuing Operation

6-

57

* 1. The default depends on the MxC capacity. The value for a 200 V class MxC of 5.5 kW is given.
* 2. These are values for a 200 V class MxC. Value for a 400 V class MxC is double.
* 3. Applicable for the Varispeed AC with software versions PRG:1050 or later.

„

Setting Precautions

Error output signals are not output during momentary power loss recovery.

To continue MxC operation after power has been restored, make settings so that Run Commands from the
control circuit terminal are stored even while power is suspended.

If the momentary power loss operation selection is set to 0 (Disabled), if the momentary power loss occurs,
alarm FDV (Power supply frequency fault) will be detected.

If the CIMR-ACA45P5, 4011, 25P5, 2011, or 2022 needs two seconds or more for the momentary power
loss ridethrough time, a separate momentary-power-loss compensation unit is required. Even if the
Momentary Power Loss Detection function (L2-01) is enabled, the MxC will run for 2 ms and then stop if
a momentary power loss occurs. Take note of this delay when the MxC is used in various applications.

A time lag of about 0.3 s can occur between the actual momentary power loss time and the momentary
power loss ridethrough time.

L2-21

Undervoltage-
detection level

Set the undervoltage-detection level for the
input power voltage in volts.

100 to

200

150

VAC

*2

No

A

A

A

Power UV Level

L2-27

*3

Detection width of
input power fre-
quency error

Sets the frequency width in hertz that detects
the input power frequency error (FDV). The
customer needs not to set or modify.

3.0 to

20.0

6.0 Hz

No

A

A

A

FDV

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector