Elevator and Hoist Type Applications

6-

153

Time Chart

Lifting

The analog signals corresponding to the load size are input as torque compensation signals from before the
MxC starts until operation stops (default: 10 V/100% torque).
Positive polarity is input for motor loads and negative polarity is input for regenerative loads.
The following diagram shows the time chart for lifting the load.

Fig 6.87 Torque Compensation Time Chart (Lifting)

Lowering

In the same way as for lifting, when the torque decreases, the analog signals corresponding to the load size are
input as torque compensation signals from before the MxC starts until operation stops (default: 10 V/100%
torque).
Negative polarity is input for motor loads and positive polarity is input for regenerative loads.

The following diagram shows the time chart for lowering.

Fig 6.88 Torque Compensation Time Chart (Lowering)

off

off

on

UP (Forward)

on

Analog signals corresponding to load size

Same as above

Torque compensation
signal: 0

HIGH/LOW

Output frequency

0

Motor torque

0

off

on

During run 2

OPEN

Holding brake operation

CLOSE

(Motor load: Inputs positive polarity.)

(Regenerative load: Inputs negative polarity.)

t

(Motor load)

(Regenerative load)

Zero-speed control

off

off

on

DOWN (Forward)

on

HIGH/LOW

Output frequency

0

Motor torque

0

off

on

During run 2

OPEN

Holding brake operation

CLOSE

(Regenerative load: Inputs positive polarity.)

(Motor load: Inputs negative polarity.)

t

(Regenerative load)

(Motor load)

Analog signals corresponding to load size

Same as above

Torque compensation
signal: 0