Continuing operation, Restarting automatically after power is restored, Related parameters – Yaskawa Matrix Converter User Manual

Page 221

Advertising
background image

6

-56

Continuing Operation

This section explains functions for continuing or automatically restarting MxC operation even if an error
occurs.

‹

Restarting Automatically after Power is Restored

Even if a temporary power loss occurs, the MxC can restart automatically after power is restored to continue
motor operation.

To restart the MxC after power is restored, set L2-01 to 1 or 2.

If L2-01 is set to 1, when power is restored within the time set in L2-02, the MxC will restart. If the time set in
L2-02 is exceeded, alarm UV1 (main circuit undervoltage) will be detected.

If L2-01 is set to 2, when the main power supply is restored while the control power supply (i.e., power supply
to the control panel) is backed up, the MxC will restart. Consequently, alarm FDEV (power supply frequency
fault) will not be detected.

„

Related Parameters

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector

L2-01

Momentary Power
Loss Detection
Selection

Enables and disables the momentary power
loss function.
0: Disabled. - MxC trips on (FDV) fault

when power is lost.

1: Power Loss Ridethrough Time - MxC will

restart if power returns within the time set
in L2-02.

2: CPU Power Active - MxC will restart if

power returns prior to control power sup-
ply shut down.

0 to 2

0

No

A

A

A

PwrL Selection

L2-02

Momentary Power
Loss Ride-thru
Time

Sets the power loss ridethrough time. This
value is dependent on the capacity of the
MxC. Enabled only when L2-01 = 1.

0 to 2.5

0.5 s

*1

No

A

A

A

PwrL Ridethru t

L2-03

Momentary Power
Loss Minimum
Base Block Time

Sets the minimum time to wait to allow the
residual motor voltage to decay before the
MxC output turns back on during power loss
ridethrough. After a power loss, if L2-03 is
greater than L2-02, operation resumes after
the time set in L2-03.

0.1 to

5.0

0.7 s

*1

No

A

A

A

PwrL Baseblock t

L2-04

Momentary Power
Loss Voltage
Recovery Ramp
Time

Sets the time it takes the output voltage to
return to the preset V/f pattern after speed
search (Current Detection Mode) is complete.

0.0 to

5.0

1.5 s

*1

No

A

A

A

PwrL V/f Ramp t

L2-05

Undervoltage
Detection Level

Sets the PS undervoltage trip level of the
MxC. If this is set lower than the default,
additional AC input reactance or PS voltage
may be necessary. Consult the factory before
changing this parameter setting.

150 to

210

*2

190

VDC

*2

No

A

A

A

PUV Det Level

L2-13

Power frequency
fault detection gain

Set the gain to detect a power frequency fault
(FDV).
If an FDV is detected when no momentary
power loss occurred, decrease the set value in
units of 0.1.

0.1 to

2.0

1.0

No

A

A

A

FDV Gain