Digital Operator Functions

6-

133

‹

Writing Parameters from the Digital Operator

If A1-01 is set to 0, the user can use the digital operator to view and set the A1 and A2 parameter groups.

If one of parameters H1-01 to H1-05 is set to 1B (meaning that “write to parameters permitted” is set one of
the multi-function digital input terminals S3 to S7), then parameter settings can be saved from the digital oper-
ator to the MxC (provided that the terminal set to 1B is switched on). When the terminal is off, writing param-
eters other than the frequency reference is prohibited. You can, however, reference other parameters.

‹

Setting a Password

When a password is set in A1-05, if the set values in A1-04 and A1-05 do not match, you cannot refer to or
change the settings of parameters A1-01 to A1-03, or A2-01 to A2-32.

You can prohibit the setting and referencing of all parameters except A1-00 by using the password function in
combination with setting A1-01 to 0 (Monitor only).

„

Related Parameters

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector

A1-01

Access Level
Selection

Used to set the parameter access level (set/
read.)
0: Monitoring only (Monitoring drive mode

and lnitialize mode.)

1: Used to select user parameter

(Only parameters set in A2-01 to A2-32
can be read and set.)

2: Advanced

(Parameters can be read and set in both
quick programming (Q) mode and
advanced programming (A) mode.)

0 to 2

2

Yes

A

A

A

Access Level

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector

A1-01

Access Level
Selection

Used to set the parameter access level (set/
read.)
0: Monitoring only (Monitoring drive mode

and lnitialize mode.)

1: Used to select user parameter

(Only parameters set in A2-01 to A2-32
can be read and set.)

2: Advanced

(Parameters can be read and set in both
quick programming (Q) mode and
advanced programming (A) mode.)

0 to 2

2

Yes

A

A

A

Access Level

A1-04

Password 1

Password input when a password has been set
in A1-05.
This function write-protects some parameters
of the initialize mode.
If the password is changed, A1-01 to A1-03
and A2-01 to A2-32 parameters can no longer
be changed. (Programming mode parameters
can be changed.)

0 to

9999

0

No

A

A

A

Enter Password