b6: Dwell Functions

„

b7: Droop Control

b5-17

PID Accel/Decel
Time

Set the accel/decel time for PID reference
in seconds.

0.0 to

25.5

0.0 s

No

A

A

A

1B5H

6-96

PID Acc/Dec
Time

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

b6-01

Dwell Reference
at Start

The dwell function is used to temporarily
hold the frequency when driving a motor
with heavy load.

0.0 to
120.0

0.0 Hz

No

A

A

A

1B6H

4-17

6-151

Dwell Ref @Start

b6-02

Dwell Time at
Start

0.0 to

10.0

0.0 s

No

A

A

A

1B7H

4-17

6-151

Dwell Time
@Start

b6-03

Dwell Frequency
at Stop

0.0 to
120.0

0.0 Hz

No

A

A

A

1B8H

4-17

6-152

Dwell Ref @Stop

b6-04

Dwell Time at
Stop

0.0 to

10.0

0.0 s

No

A

A

A

1B9H

4-17

6-152

Dwell Time
@Stop

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

b7-01

Droop Control
Level

Sets the speed decrease as a percentage of
motor base speed (E1-06) when the motor
is at 100% load torque. Setting of 0.0 dis-
ables droop control.

0.0 to
100.0

0.0

Yes

No

No

A

1CAH

4-17

6-122

Droop Quantity

b7-02

Droop Control
Delay Time

Determines the droop control delay time
in response to a load change.

0.03 to

2.00

0.05 s

Yes

No

No

A

1CBH

4-17

6-122

Droop Delay
Time

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

Run command

Output frequency

Time

on

b6-03

off

b6-01

b6-04

b6-02