Yaskawa Matrix Converter User Manual

Page 88

Advertising
background image

Test Run Procedures

4-

5

* 1. 0 or 1 for Flux Vector Control.
* 2. The setting range for accel/decel times depends on the setting of C1-10 (Accel/Decel Time Setting Unit). If C1-10 is set to 0, the setting range is 0.00 to

600.00 (s).

* 3. Fixed to 2:4 kHz for V/f.

For Open Loop Vector Control, can select from 2:4 kHz or 4:8 kHz (Fixed to 2: 4 kHz for 200 V class MxC for 45 kW and 400 V class MxCs for 22 kW

and 45 kW).

* 4. Fixed to 2: 4 kHz for 400 V class MxCs for 110 kW and 160 kW.
* 5. Displayed only while using Flux Vector Control.

E2-01

Motor Rated Cur-
rent

Sets the motor nameplate full load current in
amperes (A). This value is automatically set
during Auto-Tuning.

10% to 200%

of MxC's rated

current

Setting for

general-

purpose

motor of

same

capacity

as MxC

5-26
6-51

6-102

F1-01

*4 *5

PG Parameter

Sets the number of pulses per revolution (PPM)
of the encoder (pulse generator).

0 to 60000

600

5-29

H4-02 and

H4-05

FM and AM
terminal output
Gain

Set the voltage level gain for the multi-function
analog output 1 (H4-02) and 2 (H4-05).
Set the number of multiples of 10 V to be output
as the 100% output for the monitor item.

0.00 to 2.50

H4-02:

1.00

H4-05:

0.50

5-41

L1-01

Motor Overload
Protection Selec-
tion

Sets the motor thermal overload protection
(OL1) based on the cooling capacity of the
motor.
0: Disabled
1: General-purpose motor protection
2: Inverter motor protection
3: Vector motor protection

0 to 3

1

5-43
6-51

Table 4.1 Parameters that Must Be Set (Continued)

Parameter

Number

Name

Description

Setting

Range

Default

Page