Options

This section explains the MxC option functions.

‹

Performing Speed Control with a PG Encoder

This section explains functions with V/f Control.

„

Related Parameters

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector

F1-01

PG Parameter

Sets the number of PG (pulse generator or
encoder) pulses.
Sets the number of min

-1

.

0 to

60000

600

No

No

No

Q

PG Pulses/Rev

F1-02

Operation Selec-
tion at PG Open
Circuit (PGO)

Sets stopping method when a PG open circuit
fault (PGO) occurs. See parameter F1-14.
0: Decelerate to Stop. Decelerate to stop

using the active deceleration time.

1: Coast to Stop
2: Fast Stop. Decelerate to stop using the

deceleration time in C1-09.

3: Alarm Only - MxC continues operation.

0 to 3

1

No

No

No

A

PG Fdbk Loss Sel

F1-03

Operation Selec-
tion at Overspeed
(OS)

Sets the stopping method when an overspeed
(OS) fault occurs. See F1-08 and F1-09.
0: Decelerate to Stop. Decelerate to stop

using the active deceleration time.

1: Coast to Stop
2: Fast Stop. Decelerate to stop using the

deceleration time in C1-09.

3: Alarm Only - MxC continues operation.

0 to 3

1

No

No

No

A

PG Overspeed Sel

F1-04

Operation Selec-
tion at Deviation

Sets the stopping method when a speed devia-
tion (DEV) fault occurs. See F1-10 and F1-11.
0: Decelerate to Stop. Decelerate to stop

using the active deceleration time.

1: Coast to Stop
2: Fast Stop. Decelerate to stop using the

deceleration time in C1-09.

3: Alarm Only - MxC continues operation.

0 to 3

3

No

No

No

A

PG Deviation Sel

F1-05

PG Rotation Selec-
tion

0: Fwd = C.C.W. - Phase A leads with For-

ward Run Command (Phase B leads with
Reverse Run Command).

1: Fwd = C.W. - Phase B leads with Forward

Run Command (Phase A leads with
Reverse Run Command).

0 or 1

0

No

No

No

A

PG Rotation Sel

F1-06

PG Division Rate
(PG Pulse Moni-
tor)

Sets the division ratio for the pulse monitor of
the PG-B2 encoder feedback option card.
This function is not available with the PG-X2
option card.
Division ratio =
[(1 + n) / m] (n = 0 to 1, m =1 to 32)

The possible division ratio settings are:
1/32

≤ F1-06 ≤ 1

1 to 132

1

No

No

No

A

PG Output Ratio

F1-06

n

m