Blocking mxc outputs (baseblock commands), Time chart – Yaskawa Matrix Converter User Manual

Page 233

Advertising
background image

6

-68

‹

Blocking MxC Outputs (Baseblock Commands)

Set 8 or 9 (Baseblock Command NO/NC) in one of the parameters H1-01 to H1-10 (Terminal S3 to S12 Func-
tion Selection) to perform Baseblock Commands using the terminal's on/off operation, and prohibit MxC out-
put using the Baseblock Commands.

Clear the Baseblock Command to restart the operation using speed search from frequency references from the
previous Baseblock Command input.

Multi-Function Digital Inputs (H1-01 to H1-10)

„

Time Chart

The time chart when using Baseblock Commands is shown below.

Fig 6.49 Baseblock Commands

Set

Value

Function

Control Methods

V/f

Open

Loop

Vector

Flux

Vector

8

External baseblock NO (NO contact: Baseblock at on)

Yes

Yes

Yes

9

External baseblock NC (NC contact: Baseblock at off)

Yes

Yes

Yes

IMPORTANT

If using Baseblock Commands with a variable load, do not frequently input Baseblock Commands during run,
as this may cause the motor to suddenly start coasting, and may result in the load falling or slipping.

Forward operation/Stop

Baseblock command

Frequency reference

Output

frequency

Input

Cleared

Search from stored frequency reference

Hold

off

on