Installation orientation and clearance – Yaskawa Matrix Converter User Manual
Page 30
Advertising
Installation Orientation and Clearance
1-
11
Installation Orientation and Clearance
Install the MxC vertically so as not to reduce the cooling effect. When installing the MxC, always provide
the following installation space to allow normal heat dissipation.
Fig 1.10 MxC Installation Orientation and Clearance
IMPORTANT
1. The same space is required horizontally and vertically for both Open Chassis (IP00) and Enclosed Wall-
mounted [IP20, NEMA 1 (Type 1)] designs.
2. Always provide enough space for suspension eye bolts and the main circuit lines when installing a MxC in
a panel.
Horizontal Space
Vertical Space
120 mm min.
120 mm min.
Air
Air
50 mm min.
50 mm min.
50 mm min.
50 mm min.
30
mm
min.
30
mm
min.