5

-54

* 1. The default depends upon the MxC capacity. The value for a 200 V class MxC of 5.5 kW is given.
* 2. Applicable for the Varispeed AC with software versions PRG: 1050 or later.

„

o3: Copy Function

o2-09

Initialization
Specification
Selection

Determines parameter default values after
a full initialization (A1-03) is executed.
This should always be set to “1” for
North American installations.
0: Japanese spec
1: American spec
2: European spec

0 to 2

0

No

A

A

A

50DH

-

Init Mode Sel

o2-10

*2

Fan operation
time setting

Set the initial value of the fan operation
time using time units.
The operation time accumulates from the
set value.

0 to

65535

0

No

A

A

A

50EH

6-126
6-156

Fan ON Time Set

o2-12

Fault Trace/Fault
History Clear
Function

Clears the fault memory contained in the
U2 and U3 monitors.
0: Disabled. - no effect
1: Enabled. - resets U2 and U3 monitors,

and returns o2-12 to zero.

0 or 1

0

No

A

A

A

510H

-

FLT Trace Init

o2-14

kWh User Moni-
tor Initialization

Used to reset the kilowatt-hour monitor
U1-29 to zero.
0: Disabled. - no change
1: Enabled. - Resets U1-29 to zero and

returns o2-14 to zero.

0 or 1

0

No

A

A

A

512H

5-60

kWh Monitor Init

o2-18

*2

Capacitor
maintenance
setting

Allows the user to set the maintenance
time for the capacitors on the PCB board
(U1-61). The user can reset the accumu-
lated operation time back to zero, or to
some other desired value.

0 to 150

0%

No

A

A

A

51DH

6-156

C MaintenanceSet

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

o3-01

Copy Function
Selection

This parameter controls the copying of
parameters to and from the digital opera-
tor.
0: COPY SELECT (no function)
1: INV→ OP READ: All parameters are

copied from the MxC to the digital
operator.

2: OP → INV WRITE: All parameters

are copied from the digital operator to
the MxC.

3: OP ⇔ INV VERIFY: Parameter set-

tings in the MxC are compared to
those in the digital operator.

Note: When using the copy function, the

MxC model number (o2-04), soft-

ware number (U1-14), and control

method (A1-02) must match or an

error will occur.

0 to 3

0

No

A

A

A

515H

6-128

Copy Function
Sel

o3-02

Copy Allowed
Selection

Enables and disables the digital operator
copy functions.
0: Disabled. - No digital operator copy

functions are allowed.

1: Enabled. - Copying allowed.

0 or 1

0

No

A

A

A

516H

6-128

Read Allowable

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector