Control Circuit Wiring Precautions

Observe the following precautions when wiring control circuits.

Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, U/T1, V/T2, W/T3,
r2, s2, t2, p1, and n1) and other high-power lines.

Separate wiring for control circuit terminals MA, MB, MC, M1, and M2 (contact outputs) from wiring to
other control circuit terminals.

Use shielded twisted-pair cables for control circuits to prevent operating faults. Process cable ends as
shown in Fig 2.23.

Connect the shield wire to terminal E (G).

Insulate the shield with tape to prevent contact with other signal lines and equipment.

Use a class 2 power supply (UL standard) when connecting to the control terminals.

Fig 2.23 Processing the Ends of Shielded Twisted-Pair Cables

Shield sheath

Armor

Connect to shield sheath

terminal at MxC (terminal E (G))

Insulate with tape

Do not connect here.