Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

1019

15

Parameter reference

15.2

Parameter list | C00915

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00915

C00916

C00917

C00918

Parameter | Name:

C00915 | Motor cable length

Data type: UNSIGNED_16

Index: 23660

d

= 5C6C

h

Single motor cable length for calculating the motor cable resistance

• The calculated motor cable resistance is displayed in

C00917

.

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

m

1000.0 5.0 m

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10

Parameter | Name:

C00916 | Motor cable cross-section

Data type: UNSIGNED_16

Index: 23659

d

= 5C6B

h

Motor cable cross-section of a phase/cable for calculating the motor cable resistance

• The calculated motor cable resistance is displayed in

C00917

.

Setting range

(min. value | unit | max. value)

Lenze setting

0.50

mm^2

100.00 6.00 mm^2

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00917 | Motor cable resistance

Data type: UNSIGNED_16

Index: 23658

d

= 5C6A

h

Display of the motor cable resistance of a motor cable phase

• The motor cable resistance is calculated from the motor cable length set in

C00915

and the motor cable cross-

section set in

C00916

.

Display range

(min. value | unit | max. value)

0

mOhm

64000

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00918 | SC: Start motor magnetising current

Data type: UNSIGNED_8

Index: 23657

d

= 5C69

h

From version 10.00.00

If the servo control (

SC

) mode is selected and the controller is enabled, the speed setpoint for motor control will only

be enabled when the motor magnetising current has reached the threshold value set here.

• The adjustable percentage threshold value refers to the rated magnetising current (

C00095

).

Setting range

(min. value | unit | max. value)

Lenze setting

0

%

90 87 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1