Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

251

5

Motor control (MCTRL)

5.9

Servo control (SC)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Field weakening controller
The field weakening controller serves to adapt the magnetising current when the maximum control

voltage has been reached so that in steady operation approximately 95 % of the maximally possible

control voltage is output. Thus, there is a voltage reserve for dynamic load or speed variations.

[5-24] Recommendation for the setting of the gain and the time constant of the field weakening controller

Tip!
A field weakening controller set too slow can be recognised by the fact that the actual

speed value cannot follow the speed setpoint in the field weakening range. In this case,

carry out the setting of the field weakening controller as described in the formula. If the

speed setpoint still cannot follow the actual speed value, increase the setting in

C00577

to

maximally twice the value and reduce the setting in

C00578

according to the formula

mentioned above.
If the field weakening controller is set too fast, vibrations occur in the magnetising current,

in the direct-axis current and in the cross current, in the torque and in the speed in the field

weakening range. This is also audible by an increased motor noise (humming). The

vibrations can be dampened by a decrease of the proportional gain of the field weakening

controller.
Procedure:

• Operate the drive with max. required speed in the field weakening operation.
• Reduce Vp (

C00577

) of the field weakening controller until the vibration response

cannot be detected anymore. Increase Tn (

C00578

) according to the formula.

Parameter

Info

Lenze setting

Value Unit

C00577

SC: Vp field weakening controller

0.0010

C00578

SC: Tn field weakening controller

20.0 ms

L

m

: Mutual motor inductance (

C00092

)

L

sl

: Motor stator leakage inductance (

C00085

)

n

rated

= rated motor speed (

C00087

)

I

rated

= rated motor current (

C00088

)

V

P, FS

4774.65

L

h

[mH] L

ss

[mH]

+

L

h

[mH]

2

n

N

[rpm] I

N

[A]

------------------------------------------------------------------

=

C00577

4774.65

C00092 [mH] C00085 [mH]

+

C00092 [mH]

2

C00087 [rpm] C00088 [A]

---------------------------------------------------------------------------------------------------------------

=

T

n, FS

20 ms 0.0010

V

P, FS

-----------------

=

C00578

20 ms 0.0010

C00577

--------------------

=

Note!

Vp (

C00577

) can also be set to 0. In this case, Tn (

C00578

) should first be set to 2000 ms.