Introduction: Parameterising the controller

2.3

General notes on parameters

40

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

2.3.4

User menu for quick access to frequently used parameters

When a system is installed, parameters must be changed time and again until the system runs

satisfactorily. The user menu of the controller contains a selection of frequently used parameters to

be able to access and change these parameters quickly:

Tip!
The user menu can be freely configured in

C00517

.

In the »Engineer«, you can configure the user menu comfortably via the User menu tab (see

»Engineer« online help).
The

password protection

serves to restrict the access to parameters of the user menu. Then,

all other parameters cannot be accessed without knowing the password and are thus

protected against unwanted changes.

Parameter

Name

Lenze setting

C00051

MCTRL: Actual speed value

-

C00053

DC-bus voltage

-

C00054

Motor current

-

C00061

Heatsink temperature

-

C00137

Device status

-

C00166/3

Mess. - status det. error

-

C00011

Appl.: Reference speed

1500 rpm

C00039/1

Fixed setpoint 1

40.00 %

C00039/2

Fixed setpoint 2

60.00 %

C00012

Acceleration time - main setpoint

2.000 s

C00013

Deceleration time - main setpoint

2.000 s

C00015

VFC: V/f base frequency

50 Hz

C00016

VFC: Vmin boost

1.60 %

C00022

Imax in motor mode

depending on the device power

C00120

Setting of motor overload (I

2

xt)

100.00 %

C00087

Rated motor speed

1460 rpm

C00099

Firmware version

-

C00200

Firmware product type

-

C00105

Decel. time - quick stop

2.000 s

C00173

Mains voltage

0: "3ph 400V / 1ph 230V"

Highlighted in grey = display parameter