C00007 | control mode, C00007, De in – Lenze 8400 HighLine User Manual

Page 802: Ntrol mode in, 15 parameter reference

Advertising
background image

15

Parameter reference

15.2

Parameter list | C00007

802

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00007

Terminal assignment of the control modes 10 ... 16
Note: The following tables only list the connected inputs/outputs.

Parameter | Name:

C00007 | Control mode

Data type: UNSIGNED_16

Index: 24568

d

= 5FF8

h

With this parameter the control mode for the technology application selected under

C00005

is defined, i.e. how the

inputs and outputs of the technology application are connected to the I/Os of the controller.

• How the inputs and outputs are connected in the individual control modes is described in the corresponding

technology application:

"Actuating drive speed" TA

TA "actuating drive speed (AC Drive Profile)"

TA "Table positioning"

"Switch-off positioning" TA

Selection list

(Lenze setting printed in bold)

Info

0 Wiring has changed

This is displayed when the FB interconnection has been

changed in the I/O level via the FB Editor.

10 Terminals 0

The technology application is controlled via the digital

and analog input terminals of the controller.

• For a short overview of the preconfigured terminal

assignment see the following section "

Terminal

assignment of the control modes 10 ... 16

".

12 Terminals 2
14 Terminals 11
16 Terminal 16
20 Keypad

The technology application is controlled via the keypad.

21 PC

The technology application is controlled via the "Free

parameters" of the controller (PC control).

30 CAN

The technology application is controlled by means of

CAN-PDOs via the system bus "CAN on board".

"CAN on board" system bus

40 MCI

The technology application is controlled by means of

MCI-PDOs via the MCI-interface of an attached

communication module (e.g. PROFIBUS).

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

"Actuating drive speed" TA

Input/output

10: Terminals 0

12: Terminals 2

14: Terminals 11

16: Terminals 16

RFR

Controller enable / Reset of error message

DI1

Fixed setpoint 1/3

Change of direction of

rotation

Fixed setpoint 1/3

DI2

Fixed setpoint 2/3

Activate manual DC-

injection braking (DCB)

Fixed setpoint 2/3

DI3

Activate manual DC-injection

braking (DCB)

Quick stop

Motor potentiometer:

Increase speed

CW rotation quick stop

DI4

Change of direction of rotation

Motor potentiometer:

Decrease speed

CCW rotation quick stop

A1U, A1I

Main speed setpoint (10 V ≡ 100 % reference speed)

O1U, O1I

Actual speed value (10 V ≡ 100 % reference speed)

DO1

Status "Drive is ready"

Relay output

Status "Error is pending"