1 control characteristic, 1 control characteristic 5, 17 function library – Lenze 8400 HighLine User Manual

Page 1455

Advertising
background image

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

1455

17

Function library

17.1

Function blocks

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

17.1.134.1 Control characteristic

The PI algorithm is active in the Lenze setting.

Gain (P component)
The input value is controlled by a linear characteristic. The slope of the characteristic is determined

by the controller gain Vp.
The controller gain Vp is set under

C00222

.

• The controller gain can be adapted via the input nAdapt_a (also possible in online mode).
• The input value nAdapt_a has a direct effect on the controller gain:

Example: With the parameterised controller gain Vp = 2.0 and nAdapt_a = 75 %, the resulting gain

factor is as follows:

Integral action component (I component)
The I component can be selected via the input nISet_a. With a TRUE signal at bISet, the assigned

value is accepted in the PID controller.

• Setting the adjustment time Tn to the maximum value of "6000 ms" deactivates the I

component.

• The I component of the controller can also be deactivated by setting the input bIOff to TRUE.
• The I component can be switched on and off online.

Reset time
The adjustment time Tn is set under

C00223

.

Differential component Kd (D component)
The differential component Kd is set under

C00224

.

• The setting "0.0 s" deactivates the D component (Lenze setting). In this way, the PID controller

becomes a PI controller or P controller, if the I component has been deactivated as well.

P

nAdapt_a C00222

=

P

75 [%]

100 [%]

-------------------

2.0

1.5

=

=

Advertising