I-1a00, I-1a01, 11 system bus "can on board – Lenze 8400 HighLine User Manual

Page 764

Advertising
background image

11

System bus "CAN on board"

11.11

Implemented CANopen objects | I-1A00

764

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

I-1A00

The object I-1A00 serves to send parameter data as TPDO1.

• This object relates to code

C00868/1...4

.

[11-16] Data telegram assignment

IEC 61131 process data words are mapped. Only whole bytes can be mapped (1-byte/mapping

entry).

Related topics:

TPDO1 | "LP_CanOut1" port block

( 712)

I-1A01

The object I-1A01 serves to send parameter data as TPDO2.

• This object relates to code

C00868/5...8

.

• For data telegram assignment, see object

I-1A00

.

Related topics:

TPDO2 | "LP_CanOut2" port block

( 713)

Index:

I-1A00

Name:

TPDO1 mapping parameter

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Number of mapped application

objects in PDO

0

0

8 rw

U8

1 ... 4: Application object 1 ... 4

0

0

4294967295 rw

U32

Subindex

Meaning

0

Number of mapped objects

1 ... 4

Mapping entries 1 ... 4 for TPDO1

• The 4th mapping entry is used for the statistic mapping. For this, there is no value

available.

8th byte

7th byte

6th byte

5th byte

Data 4

Data 3

Data 2

Data 1

Bit 31 ... bit 16

Bit 15 ... bit 8

Bit 7 ... bit 0

Index

Subindex

Length

Index:

I-1A01

Name:

TPDO2 mapping parameter

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Number of mapped application

objects in PDO

0

0

8 rw

U8

1 ... 4: Application object 1 ... 4

0

0

4294967295 rw

U32

Subindex

Meaning

0

Number of mapped objects

1 ... 4

Mapping entries 1 ... 4 for TPDO2

• The 4th mapping entry is used for the statistic mapping. For this, there is no value

available.

Advertising