Motor control (MCTRL)

5.5

V/f characteristic control - energy-saving (VFCplusEco)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.5.4

Optimising the control mode

The V/f characteristic control - energy-saving (VFCplus) is generally ready for operation. It can be

adapted subsequently by adapting the characteristic and/or the drive behaviour.

Adapting characteristic
For the linear characteristic as part of the V/f characteristic control - energy-saving (VFCplusEco), it

is also possible (like in case of the standard V/f characteristic control) to match its curve to different

load profiles or motors by adapting the V/f base frequency (

C00015

) and the V

min

boost (

C00016

).

Adapting the V/f base frequency

( 161)

Adapting the Vmin boost

( 163)

Adapting drive behaviour

• Limitation of the maximum current by a current limitation controller (e.g. to prevent the motor

from stalling or to limit to the maximally permissible motor current).

Optimising the Imax

controller

( 164)

• Adaptation of the field frequency by a load-dependent slip compensation (improved speed

accuracy for systems without feedback).

Improving the behaviour at high dynamic load changes

.

( 178)

Adapting the slope limitation for lowering the Eco function

.

( 179)

Optimising the cos/phi controller

.

( 179)

Torque limitation
Limit the torque to a lower value.

Torque limitation

( 166)

Note!

Following successful motor parameter identification, the V/f base frequency (

C00015

)

and the V

min

boost (

C00016

) as well as the slip constant for slip compensation (

C00021

)

are calculated automatically.

From version 12.00.00

onwards:

• Following successful motor parameter identification, the gain of the Imax controller

(

C00073/1

) is calculated automatically.

• If these parameters are not to be calculated, bit 4 of

C02865/1

must be set to "1".

• Following successful motor parameter identification, other controller parameters

(

C00011

,

C00022

,

C00966

,

C00982

) can be calculated automatically.

• If these parameters are to be calculated, bit 6 of

C02865/1

must be set to "6".