Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

859

15

Parameter reference

15.2

Parameter list | C00252

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00252

C00253

C00254

C00265

C00270

Parameter | Name:

C00252 | L_DT1_1: Gain

Data type: INTEGER_16

Index: 24323

d

= 5F03

h

FB

L_DT1_1

: Gain factor Vp

Setting range

(min. value | unit | max. value)

Lenze setting

-320.00

320.00 1.00

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00253 | L_DT1_1: Sensitivity

Data type: UNSIGNED_8

Index: 24322

d

= 5F02

h

FB

L_DT1_1

: Selection of sensitivity

• Depending on the selection, the number of indicated higher-order bits is evaluated.

Note:

The most significant bit determines the sign of the value, the remaining bits determine the numerical value.
Selection list

(Lenze setting printed in bold)

Info

1 15 bits

Bit 0 ... bit 14 are evaluated

2 14 bits

Bit 0 ... bit 13 are evaluated

3 13 bits

Bit 0 ... bit 12 are evaluated

4 12 bits

Bit 0 ... bit 11 are evaluated

5 11 Bit

Bit 0 ... bit 10 are evaluated

6 10 Bit

Bit 0 ... bit 9 are evaluated

7 9 Bit

Bit 0 ... bit 8 are evaluated

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00254 | Kp position controller

Data type: UNSIGNED_16

Index: 24321

d

= 5F01

h

Gain for following error compensation
Setting range

(min. value | unit | max. value)

Lenze setting

0.00

1/s

500.00 5.00 1/s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00265 | SLVC: Tn torque controller

Data type: UNSIGNED_8

Index: 24310

d

= 5EF6

h

This code is for device-internal use only and must not be written to by the user!

Parameter | Name:

C00270 | SC: Freq. current setpoint filter

Data type: UNSIGNED_16

Index: 24305

d

= 5EF1

h

Frequency to be inhibited by the current setpoint filter at servo control (

SC

) and sensorless control for synchronous

motors (

SLPSM

).

Setting range

(min. value | unit | max. value)

Lenze setting

40.0

Hz

1000.0 200.0 Hz

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10