Commissioning

3.6

Manual motor direction of rotation check (manual control)

56

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3.6

Manual motor direction of rotation check (manual control)

The »Engineer« function "Manual control" easily allows for controlling the direction of rotation of

the motor. The manual control serves to let the motor connected to the controller with an

adjustable speed for an adjustable time.

How to carry out a manual motor direction of rotation check using the »Engineer«:

1. In the Project view, select the 8400 HighLine controller.

2.

Go online.

After a connection to the controller has been established, the following status is displayed

in the Status line:

3. Click the

symbol to inhibit the controller via device command.

4. Ensure that the following conditions are met:

• The mains voltage is switched on.
• No trouble is active.
• Safe torque off (STO) is not active.

5. Enable controller via terminal: Set terminal X5/RFR to HIGH level.

6. Click the

icon to open the Manual motor rotation indication dialog box.

Note: If the "not ready for operation" status is displayed, check whether all conditions

mentioned before (see steps 3 ... 5) have been met.

7. Set the desired speed and runtime.

(The speed refers to the reference speed set in

C00011

.)

8. Click the

button to let the motor rotate with the set speed for the set runtime.

By clicking the

button, the function can be aborted.

Note!

Take all the necessary safety precautions before you carry out the following

commissioning steps and switch the device on!