925

15

Parameter reference

15.2

Parameter list | C00605

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00605

C00606

C00607

C00608

Parameter | Name:

C00605 | Resp. to feedback

Data type: UNSIGNED_8

Index: 23970

d

= 5DA2

h

From version 15.00.00

Selection list

0 No Reaction
1 Fault
2 Trouble
3 TroubleQuickStop
4 WarningLocked
5 Warning
6 Information

Subcodes

Lenze setting

Info

C00605/1

1: Fault

Resp. to open circuit HTL 4-fold

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00606 | Resp. to motor overload (I²xt)

Data type: UNSIGNED_8

Index: 23969

d

= 5DA1

h

Response when the motor load displayed in

C00066

reaches the value "100.00 %".

Motor overload monitoring (I2xt)

Selection list

(Lenze setting printed in bold)

0 No Reaction
1 Fault
5 Warning

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00607 | Resp. to max freq. feedb. DIG12/67

Data type: UNSIGNED_8

Index: 23968

d

= 5DA0

h

Response when the maximum input frequency has been reached via the digital inputs.
Selection list

(Lenze setting printed in bold)

0 No Reaction
1 Fault
5 Warning

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00608 | Resp. to maximum torque

Data type: UNSIGNED_8

Index: 23967

d

= 5D9F

h

Response if the maximum torque (

C00057

) is reached.

Selection list

(Lenze setting printed in bold)

0 No Reaction
1 Fault
5 Warning

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1