C02865 | mctrl: special settings, C02865/1, Bit 6 of – Lenze 8400 HighLine User Manual

Page 1142: C02865, Has no effect on the, Must be set, C2865/1, 15 parameter reference

Advertising
background image

15

Parameter reference

15.2

Parameter list | C02865

1142

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C02865

Bit 8 Suppress V/f emergency operation

From version 15.00.00

, it is internally switched to the

encoderless V/f characteristic control in case of a motor

control type with feedback and an encoder open circuit

in order to avoid impermissible motor movements.

• In order that this "V/f emergency operation" works

properly, the parameters relevant for the V/f

characteristic control (base frequency, Vmin boost,

slip compensation, etc.) have to be set correctly. As an

alternative, a motor parameter identification can be

executed as well.

• The change-over to "V/f emergency operation" is

reported via bit 4 in

C01000

and via the

bWirebreakUfLinearActive status signal at the

SB

LS_DeviceMonitor

.

• The setting in

C00006

is not affected by the change-

over.

The "V/f emergency operation" can be suppressed by

setting bit 8 to "1".

0 ≡ V/f emergency operation in case of encoder open

circuit

1 ≡ No V/f emergency operation in case of encoder open

circuit

Bit 9

Reserved

Bit 10

Reserved

Bit 11

Reserved

Bit 12

Reserved

Bit 13

Reserved

Bit 14

Reserved

Bit 15

Reserved

Subcodes

Lenze setting

Info

C02864/1

0x0000

MCTRL

: Optimisations

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Parameter | Name:

C02864 | MCTRL: Optimisiations

Data type: UNSIGNED_16

Index: 21711

d

= 54CF

h

Parameter | Name:

C02865 | MCTRL: Special settings

Data type: UNSIGNED_16

Index: 21710

d

= 54CE

h

From version 12.00.00

Activation of special functions of the internal motor control
Setting range

(min. hex value | max. hex value)

0x0000

0xFFFF

Value is bit-coded:

Info

Bit 0 No TorqueLimit if TorquemodeOn

From version 12.00.00 onwards

: If sensorless vector

control (

SLVC

) or servo control (

SC

) are used, in the

"torque control with speed limitation" mode the torque

limitation via nTorqueMotLimit_a and

nTorqueGenLimit_a is also active to limit the torque

setpoint.

If you want to deactivate the torque limitation to retain

the former function, set bit 0 to "1".

0 ≡ Torque limitation is active

1 ≡ Torque limitation is not active

Bit 1 250ms IMP before DCB
Bit 2 1000ms IMP before DCB