C01108 | l_switchpoint_1: dead time factor, C01120 | sync signal source, C01121 | sync cycle time setpoint – Lenze 8400 HighLine User Manual

Page 1057: C01121, C01120, Ed in, Selected in, 15 parameter reference

Advertising
background image

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

1057

15

Parameter reference

15.2

Parameter list | C01108

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C01108

C01120

C01121

Parameter | Name:

C01108 | L_SwitchPoint_1: Dead time factor

Data type: UNSIGNED_8

Index: 23467

d

= 5BAB

h

From version 14.00.00

Selection list

1 1 μs
2 10 μs
3 100 μs
4 1000 μs

Subcodes

Lenze setting

Info

C01108/1

2: 10 μs

L_SwitchPoint_1

: Deadtime factor 1

C01108/2

2: 10 μs

L_SwitchPoint_1

: Deadtime factor 2

C01108/3

2: 10 μs

L_SwitchPoint_1

: Deadtime factor 3

C01108/4

2: 10 μs

L_SwitchPoint_1

: Deadtime factor 4

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C01120 | Sync signal source

Data type: UNSIGNED_8

Index: 23455

d

= 5B9F

h

From version 02.00.00

Selection of the signal source for device synchronisation

• The drive can only be synchronised by one source.

Synchronisation of the internal time base

Selection list

(Lenze setting printed in bold)

Info

0 Off

Synchronisation off

1 CAN on board

Synchronisation via CAN bus

Sync telegram

4 MCI

Synchronisation via MCI (communication module)

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C01121 | Sync cycle time setpoint

Data type: UNSIGNED_16

Index: 23454

d

= 5B9E

h

From version 04.00.00

Cycle time setpoint for device synchronisation

• Time interval at which the phase control loop (PLL) in the controller expects the synchronisation signals.

• The cycle time setpoint must be set according to the cycle of the respective synchronisation source.

Note:

• Only integer multiples of 1000 μs can be set.

• Intelligent communication modules usually define the cycle time setpoint derived from the bus cycle. In this

case, a manual change is not possible.

Example: For the CAN bus, a distance of 2 ms has been set between two synchronisation signals. If the CAN bus is

to be used as synchronisation source, a synchronisation cycle of 2000 μs must be set in C01121.

Synchronisation of the internal time base

Setting range

(min. value | unit | max. value)

Lenze setting

1000

μs

20000 1000 μs

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1