Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

947

15

Parameter reference

15.2

Parameter list | C00680

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00680

C00681

C00682

C00685

Parameter | Name:

C00680 | L_Compare_1: Fct.

Data type: UNSIGNED_8

Index: 23895

d

= 5D57

h

The

L_Compare_1

FB: Comparison operation

• If the statement of the selected comparison operation is true, the binary bOut output will be set to TRUE.

Selection list

(Lenze setting printed in bold)

1 In1 = In2
2 In1 > In2
3 In1 < In2
4 |In1| = |In2|
5 |In1| > |In2|
6 |In1| < |In2|

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00681 | L_Compare_1: Hysteresis

Data type: INTEGER_16

Index: 23894

d

= 5D56

h

The

L_Compare_1

FB: Hysteresis for the comparison function selected in

C00680

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

%

100.00 0.50 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00682 | L_Compare_1: Window

Data type: INTEGER_16

Index: 23893

d

= 5D55

h

The

L_Compare_1

FB: Window for the comparison function selected in

C00680

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

%

100.00 2.00 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00685 | L_Compare_2: Fct.

Data type: UNSIGNED_8

Index: 23890

d

= 5D52

h

The

L_Compare_2

FB: Comparison operation

• If the statement of the selected comparison operation is true, the binary bOut output will be set to TRUE.

Selection list

(Lenze setting printed in bold)

1 In1 = In2
2 In1 > In2
3 In1 < In2
4 |In1| = |In2|
5 |In1| > |In2|
6 |In1| < |In2|

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1