Parameter list | C00059

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00059

C00061

C00062

C00064

Parameter | Name:

C00059 | Appl.: Reference frequency C11

Data type: UNSIGNED_32

Index: 24516

d

= 5FC4

h

Display of the field frequency which corresponds to the reference speed set in

C00011

.

Display range

(min. value | unit | max. value)

0.00

Hz

1300.00

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00061 | Heatsink temperature

Data type: INTEGER_16

Index: 24514

d

= 5FC2

h

Display of the current heatsink temperature
Display range

(min. value | unit | max. value)

-50

°C

150

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00062 | Temperature inside the controller

Data type: INTEGER_16

Index: 24513

d

= 5FC1

h

From version 11.00.00

Display of the current temperature inside the controller
Display range

(min. value | unit | max. value)

-200

°C

200

Subcodes

Info

C00062/1

Interior temperature of CU

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00064 | Device utilisation (Ixt)

Data type: INTEGER_16

Index: 24511

d

= 5FBF

h

Display of the device utilisation Ixt in different time resolutions

• If the value displayed here exceeds the threshold set in

C00123

, the fault message "OC5: Device overload (Ixt)"

is output and the fault response set in

C00604

is executed (default setting: "Warning").

Display range

(min. value | unit | max. value)

0.00

%

250.00

Subcodes

Info

C00064/1

Device utilisation (Ixt)

• Maximum value of the pulse utilisation (C00064/2)

and permanent utilisation (C00064/3).

C00064/2

Device utilisation (Ixt) 15s

• Pulse utilisation over the last 15 seconds (only for

loads >160 %).

C00064/3

Device utilisation (Ixt) 3 min

• Permanent utilisation over the last 3 minutes.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100