Xx.0131.00006, Xx.0131.00007, Xx.0131.00008 – Lenze 8400 HighLine User Manual

Page 657: Xx.0131.00011, Xx.0131.00000, 9diagnostics & error management

Advertising
background image

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

657

9

Diagnostics & error management

9.9

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

CE4: CAN bus off [xx.0131.00000]

CA06: CAN CRC error [xx.0131.00006]

CA07: CAN bus warning [xx.0131.00007]

CA08: CAN bus stopped [xx.0131.00008]

CA0b: CAN HeartBeatEvent [xx.0131.00011]

Response (Lenze setting printed in bold)

Setting:

C00592/2

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

CAN on board

: "Bus off" status

• Received too many faulty telegrams.

• Damaged cable (e.g. loose contact).

• Two nodes with the same ID.

• Check wiring and bus terminating resistor.

• Set identical baud rate for each bus node.

• Assign different IDs to nodes.

• Eliminate electrical interference (e.g. EMC).

Response (Lenze setting printed in bold)

Setting:

C00592/1

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

CAN on board

: A faulty CAN telegram has been detected.

• Check wiring and bus terminating resistor.

• Eliminate electrical interference (e.g. EMC).

Response (Lenze setting printed in bold)

Setting:

C00592/3

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

CAN on board

: Incorrect transmission or reception of

more than 96 CAN telegrams.

• The current number of incorrectly transmitted CAN

telegrams is displayed in

C00372/1

.

• The current number of incorrectly received CAN

telegrams is displayed in

C00372/2

.

• The current CAN error status is displayed in

C00345

.

• Check wiring and bus terminating resistor.

• Set identical baud rate for each bus node.

• Assign different IDs to nodes.

• Eliminate electrical interference (e.g. EMC).

Response (Lenze setting printed in bold)

Setting:

C00592/4

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

CAN on board

: The device has received the "Stop Remote

Node" NMT telegram.

Check CAN master (NMT master).

Response (Lenze setting printed in bold)

Setting:

C00592/5

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

CAN on board

: Cyclic node monitoring

• Being a Heartbeat consumer, the device has not

received a Heartbeat telegram from Heartbeat

producer 1 ... 15 within the defined time.

• The current states of the Heartbeat producers are

displayed in

C00347/1...15

.

• Reactivate Heartbeat producers by mains switching,

restarting the controller, or a CAN Reset Node.

• Reparameterise CAN Heartbeat producer time or

switch off consumer monitoring and reset error

status if latched.

Heartbeat protocol