C00959 | l_curve: current output value, C00960 | l_curve_1: selected curve type, C00961 | l_curve_1: input limitation – Lenze 8400 HighLine User Manual

Page 1023: 15 parameter reference

Advertising
background image

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

1023

15

Parameter reference

15.2

Parameter list | C00959

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00959

C00960

C00961

Parameter | Name:

C00959 | L_Curve: Current output value

Data type: INTEGER_16

Index: 23616

d

= 5C40

h

From version 11.00.00

FB

L_Curve_1

: Display of the current output value nOut_a

Display range

(min. value | unit | max. value)

-199.99

%

199.99

Subcodes

Info

C00959/1

L_Curve_1

: Current output value

C00959/2

L_Curve_2

: Current output value

C00959/3

L_Curve_3

: Current output value

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00960 | L_Curve_1: Selected curve type

Data type: UNSIGNED_8

Index: 23615

d

= 5C3F

h

From version 04.00.00

FB

L_Curve_1

: Selected curve type

Selection list

0 Out = 0
1 Out = In
2 Out = f(In)
3 Out = f(table)

Subcodes

Lenze setting

Info

C00960/1

1: Out = In

L_Curve_1

: Function

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00961 | L_Curve_1: Input limitation

Data type: INTEGER_16

Index: 23614

d

= 5C3E

h

From version 04.00.00

FB

L_Curve_1

: Upper and lower limit for input value

Setting range

(min. value | unit | max. value)

-199.99

%

199.99

Subcodes

Lenze setting

Info

C00961/1

199.99 %

L_Curve_1

: Max. input

C00961/2

-199.99 %

L_Curve_1

: Min. input

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100