C00725

C00726

Parameter | Name:

C00725 | Current switching frequency

Data type: UNSIGNED_8

Index: 23850

d

= 5D2A

h

Display of the current switching frequency

• In

C00018

you can choose between a drive-optimised setting for good smooth-running characteristics and an

inverter loss-optimised setting (min. Pv).

• Both possibilities offer fixed and variable switching frequencies.

• When a variable switching frequency is selected in

C00018

, the switching frequency may change as a function

of the load and rotational frequency.

Selection list

(read only)

1 4 kHz var./drive-optimised
2 8 kHz var./drive-optimised
3 16 kHz var./drive-optimised
5 2 kHz constant/drive-optimised
6 4 kHz constant/drive-optimised
7 8 kHz constant/drive-optimised
8 16 kHz constant/drive-optimised

11 4 kHz var./min. Pv
12 8 kHz var./min. Pv
13 16 kHz var./min. Pv
14 Reserved
15 2 kHz constant/min. Pv
16 4 kHz constant/min. Pv
17 8 kHz constant/min. Pv
18 16 kHz constant/min. Pv
21 8 kHz var./drive-opt./4 kHz min
22 16 kHz var./drive-opt./4 kHz min
23 16 kHz var./drive-opt./8 kHz min
31 8 kHz var./min. Pv/4 kHz min
32 16 kHz var./min. Pv/4 kHz min
33 16 kHz var./min. Pv/8 kHz min

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00726 | Current limit values

Data type: UNSIGNED_8

Index: 23849

d

= 5D29

h

This code is for device-internal use only and must not be written to by the user!