Motor control (MCTRL)

5.4

V/f characteristic control (VFCplus)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

V/f characteristic control (VFC)
The accuracy of the torque limitation is limited because the actual torque (

C00056/2

) is only

calculated from the slip speed measured indirectly via the motor current.

V/f control (VFC + encoder)
The slip speed of the motor is available at the slip controller output. This leads to a high accuracy for

the actual torque (

C00056/2

) and the torque limitation.

[5-6]

Extract from the signal flow of the V/f control (VFC + encoder)

Parameter

Info

Parameter

Info

1

C00056/2

Actual torque value

9

C00830/22

MCTRL: nSpeedSetValue_a

2

C00830/29

Limitation of torque in motor mode

10

C00909/1

Max. pos. speed

3

C00830/28

Limitation of torque in generator mode

11

C00909/2

Max. neg. speed

4

C00054

Motor current

12

C00105

Decel. time - quick stop

5

C00022

Imax in motor mode

13

C00050

Speed setpoint

6

C00023

Imax in generator mode

7

C00074

Ti Imax controller

8

C00073

Vp Imax controller